Beacon 200 Two Channel
Wall Mount Controller

  • Simultaneous readout on 2 channels
  • Two alarm levels per channel
  • Discrete and common relays
  • NEMA 4X enclosure
  • 4-20 mA outputs
  • Proven, long-life sensors for a wide variety of gases
  • Accepts any 4-20 mA transmitter input (24 VDC)
  • Easy to install, operate and expand

    Contact Our Sales





    • Description
    • Features
    • Applications
    • Specifications
    • Download

    The Beacon 200 is a powerful, low cost fixed system controller for two points of gas detection. It is microprocessor controlled, versatile, simple to install and operate, and priced to be the industry’s most economical two point controller. It is capable of connecting directly to RKI sensors for LEL level combustibles, Oxygen, Hydrogen Sulfide, or Carbon Monoxide. The Beaconª 200 can also accept any 4-20 mA transmitter (2 or 3 wire, 24 VDC). Sensors can be mounted directly at the Beaconª 200 housing, or can be wired remotely from the controller.

    The 10 amp rated relays are strong enough to actuate most external alarms and horns without using slave relays. The digital display has backlighting and simultaneous readout of the gas type and concentration.

    The Beaconª 200’s housing is rated NEMA 4X for corrosion resistance and a weather tight seal, and complies with lock out / tag out standards. An external reset switch allows the alarm to be silenced from outside of the controller housing. The Beaconª 200 comes complete with a wall mounting kit for easy installation.

    RKI offers the industry’s widest selection of standard and toxic gas detection sensors, which can be utilized with the Beaconª 200, providing gas monitoring protection for almost any application.

    • Simultaneous readout on 2 channels
    • Two alarm levels per channel
    • Discrete and common relays
    • NEMA 4X enclosure
    • 4-20 mA outputs
    • Proven, long-life sensors for a wide variety of gases
    • Accepts any 4-20 mA transmitter input (24 VDC)
    • Easy to install, operate and expand
    • Petrochemical plants
    • Refineries
    • Water & wastewater treatment plants
    • Pulp & paper mills
    • Gas, telephone, & electric utilities
    • Parking garages
    • Manufacturing facilities
    • Steel
    • Automotive
    • HVAC

    Physical

    DimensionsHeight: 10.5” 267 mm Width: 8.5” 216 mm Depth: 6.3” 158 mm
    EnclosureWall mounting grey polycarbonate with hinged cover
    Conduit
    Connection
    3/4” NPT conduit hubs, 3 provided. 2 for sensor wiring and 1 for power & relay wiring
    Wiring
    Termination
    Screw type terminal block, 14 gauge max
    Controls
    4 internal push buttons for setup, programming, and calibration. 1 external push button for alarm reset

    Environmental

    Operating Temp-4°F to 122°F (-10°C to 50°C)
    Storage Temp-4°F to 158°F (-20°C to 70°C)
    Relative
    Humidity
    0 – 100% RH
    Enclosure
    Rating
    NEMA-4X enclosure, waterproof, chemical, and weather resistant

    Inputs

    Direct Wired SensorsLEL, Oxygen, Carbon Monoxide, Hydrogen Sulfide
    Remote amp not required for less than 500 feet
    4-20 mA SensorsAccepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals. (See list of detectable gases.) Wiring distances up to 5000 feet
    Sampling MethodsDiffusion and sample draw heads available

    Outputs

    Relays7 relays – 10 amp rating (at 115 VAC), SPDT isolated contacts. 2 relays for gas alarm levels per channel, plus 2 relays for common gas alarm and 1 common relay for malfunction. Relays fully programmable for: increasing or decreasing alarm, latching or self reset, normally energized or normally de-energized, time delay for alarm on and alarm off
    4-20 mASignal output, 4-20 mA (into 1000 ohms impedance maximum), per channel
    24 VDC24 VDC (350 mA max) output provided to operate sample drawing adapters or other accessories
    DisplayAlphanumeric display with backlighting. 20 characters per line; 4 lines each
    AudibleBuilt-in audible alarm, 94 dB, mounted on enclosure
    Coded output: pulsing = gas alarm, steady = fail
    Visual4 LED’s on the front cover for alarm status indication, pilot, and malfunction
    Optional
    Expansion Cards
    Individual 4-20 mA (or 1 – 5 VDC) outputs
    Heavy duty relay card (4 each @ 30 amps)

    Power

    110-240 VAC or 24 VDC standard. Battery backup option available

    Warranty

    One year materials and workmanship
    Partial List Of Detectable Gases
    Many other gases or ranges available. Contact RKI for gases or ranges not listed.
    Ammonia (NH3)
    0 – 75.0 ppm
    Arsine (AsH3 )0 – 0.20 ppm
    Boron Trichloride (BCl3)0 – 15.0 ppm
    Carbon Dioxide (CO2)0 – 1.0 %
    Carbon Monoxide (CO)0 – 300 ppm
    Chlorine (Cl2)0 – 3.0 ppm
    Chlorine Dioxide (ClO2)0 – 1.00 ppm
    Chlorine Trifluoride (ClF3)0 – 1.00 ppm
    Combustibles0 -100% LEL
    Diborane (B2H6)0 – 30.0 ppm
    Fluorine (F2)0 – 6.0 ppm
    Hydrogen (H2)0 – 2000 ppm
    Hydrogen Chloride (HCl)0 – 15.0 ppm
    Hydrogen Fluoride (HF)0 – 9.0 ppm
    Hydrogen Sulfide (H2S)0 -100.0 ppm
    Nitric Oxide (NO)0 -100.0 ppm
    Nitrogen Dioxide (NO2)0 – 15.0 ppm
    Nitrogen Trifluoride (NF3)0 – 30.0 ppm
    Oxygen (O2)0 – 25.0 %
    Ozone (O3)0 – 1.0 ppm
    Phosphine (PH3)0 – 1.0 ppm
    Silane (SiH4)0 – 15.0 ppm
    Sulfur Dioxide (SO2)0 – 30.0 ppm
    TEOS (Si(OC2H5)4)0 -15/30 ppm

    Specifications subject to change without notice.
    Made in the USA

    Click Here For Download pdf File

    DatasheetManual