Beacon 200 Two Channel
Wall Mount Controller

  • Simultaneous readout on 2 channels
  • Two alarm levels per channel
  • Discrete and common relays
  • NEMA 4X enclosure
  • 4-20 mA outputs
  • Proven, long-life sensors for a wide variety of gases
  • Accepts any 4-20 mA transmitter input (24 VDC)
  • Easy to install, operate and expand

The Beacon 200 is a powerful, low cost fixed system controller for two points of gas detection. It is microprocessor controlled, versatile, simple to install and operate, and priced to be the industry’s most economical two point controller. It is capable of connecting directly to RKI sensors for LEL level combustibles, Oxygen, Hydrogen Sulfide, or Carbon Monoxide. The Beaconª 200 can also accept any 4-20 mA transmitter (2 or 3 wire, 24 VDC). Sensors can be mounted directly at the Beaconª 200 housing, or can be wired remotely from the controller.

The 10 amp rated relays are strong enough to actuate most external alarms and horns without using slave relays. The digital display has backlighting and simultaneous readout of the gas type and concentration.

The Beaconª 200’s housing is rated NEMA 4X for corrosion resistance and a weather tight seal, and complies with lock out / tag out standards. An external reset switch allows the alarm to be silenced from outside of the controller housing. The Beaconª 200 comes complete with a wall mounting kit for easy installation.

RKI offers the industry’s widest selection of standard and toxic gas detection sensors, which can be utilized with the Beaconª 200, providing gas monitoring protection for almost any application.

  • Simultaneous readout on 2 channels
  • Two alarm levels per channel
  • Discrete and common relays
  • NEMA 4X enclosure
  • 4-20 mA outputs
  • Proven, long-life sensors for a wide variety of gases
  • Accepts any 4-20 mA transmitter input (24 VDC)
  • Easy to install, operate and expand
  • Petrochemical plants
  • Refineries
  • Water & wastewater treatment plants
  • Pulp & paper mills
  • Gas, telephone, & electric utilities
  • Parking garages
  • Manufacturing facilities
  • Steel
  • Automotive
  • HVAC

Physical

 
DimensionsHeight: 10.5” 267 mm Width: 8.5” 216 mm Depth: 6.3” 158 mm
EnclosureWall mounting grey polycarbonate with hinged cover
Conduit
Connection
3/4” NPT conduit hubs, 3 provided. 2 for sensor wiring and 1 for power & relay wiring
Wiring
Termination
Screw type terminal block, 14 gauge max
Controls
4 internal push buttons for setup, programming, and calibration. 1 external push button for alarm reset
  

Environmental

 
Operating Temp-4°F to 122°F (-10°C to 50°C)
Storage Temp-4°F to 158°F (-20°C to 70°C)
Relative
Humidity
0 – 100% RH
Enclosure
Rating
NEMA-4X enclosure, waterproof, chemical, and weather resistant
  

Inputs

 
Direct Wired SensorsLEL, Oxygen, Carbon Monoxide, Hydrogen Sulfide
Remote amp not required for less than 500 feet
4-20 mA SensorsAccepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals. (See list of detectable gases.) Wiring distances up to 5000 feet
Sampling MethodsDiffusion and sample draw heads available
  

Outputs

 
Relays7 relays – 10 amp rating (at 115 VAC), SPDT isolated contacts. 2 relays for gas alarm levels per channel, plus 2 relays for common gas alarm and 1 common relay for malfunction. Relays fully programmable for: increasing or decreasing alarm, latching or self reset, normally energized or normally de-energized, time delay for alarm on and alarm off
4-20 mASignal output, 4-20 mA (into 1000 ohms impedance maximum), per channel
24 VDC24 VDC (350 mA max) output provided to operate sample drawing adapters or other accessories
DisplayAlphanumeric display with backlighting. 20 characters per line; 4 lines each
AudibleBuilt-in audible alarm, 94 dB, mounted on enclosure
Coded output: pulsing = gas alarm, steady = fail
Visual4 LED’s on the front cover for alarm status indication, pilot, and malfunction
Optional
Expansion Cards
Individual 4-20 mA (or 1 – 5 VDC) outputs
Heavy duty relay card (4 each @ 30 amps)
  

Power

110-240 VAC or 24 VDC standard. Battery backup option available
  

Warranty

One year materials and workmanship
Partial List Of Detectable Gases
Many other gases or ranges available. Contact RKI for gases or ranges not listed.
Ammonia (NH3)
0 – 75.0 ppm
Arsine (AsH3 )0 – 0.20 ppm
Boron Trichloride (BCl3)0 – 15.0 ppm
Carbon Dioxide (CO2)0 – 1.0 %
Carbon Monoxide (CO)0 – 300 ppm
Chlorine (Cl2)0 – 3.0 ppm
Chlorine Dioxide (ClO2)0 – 1.00 ppm
Chlorine Trifluoride (ClF3)0 – 1.00 ppm
Combustibles0 -100% LEL
Diborane (B2H6)0 – 30.0 ppm
Fluorine (F2)0 – 6.0 ppm
Hydrogen (H2)0 – 2000 ppm
Hydrogen Chloride (HCl)0 – 15.0 ppm
Hydrogen Fluoride (HF)0 – 9.0 ppm
Hydrogen Sulfide (H2S)0 -100.0 ppm
Nitric Oxide (NO)0 -100.0 ppm
Nitrogen Dioxide (NO2)0 – 15.0 ppm
Nitrogen Trifluoride (NF3)0 – 30.0 ppm
Oxygen (O2)0 – 25.0 %
Ozone (O3)0 – 1.0 ppm
Phosphine (PH3)0 – 1.0 ppm
Silane (SiH4)0 – 15.0 ppm
Sulfur Dioxide (SO2)0 – 30.0 ppm
TEOS (Si(OC2H5)4)0 -15/30 ppm

Specifications subject to change without notice.
Made in the USA

Click Here For Download pdf File

Datasheet • Manual