GD-70D Series Intelligent Gas Detector
- Monitor combustibles, O2, and a wide range of toxics
- Plug and play smart sensors retain calibration and sensor data
- Common platform (Main unit / Sensor / Pump) for all detection methods
- Universal main unit (all sensor types)
- Multifunctional sensor unit (New Intelligent sensor)
- No internal tubing (main unit) / No coil (pump)
- Front access, no tool required, easy sensor and pump replacement
- Large size LCD screen
- Various communication methods available (4-20mA, NT and PoE)
- Minimal maintenance cost through enhanced troubleshooting firmware functions
- Small mounting space
- Environmentally friendly
- Wide variety of sensors available
- Description
- Features
- Gases
- Specifications
- Download
The new Model GD-70D smart gas detection transmitter series sets a new standard for performance, flexibility, and versatility. The GD-70D sample-draw transmitter offers an array of sensor technologies unmatched in the industry, including unique offerings, such as our hydrogen-specific or LEL versions.
The long life high capacity pump and wide variety of sensing elements are replaceable in a few seconds, with no tools required! The smart sensors retain all calibration and sensor-specific data in non-volatile memory, so sensors can be hot-swapped in the field with no programming required. The sensors also retain calibration information, which means they can be conveniently calibrated separate from the transmitter, avoiding transport of calibration gases to the field location. The GD-70D firmware automatically corrects for long-term zero and span “drift” minimizing maintenance and maximizing reliability.
The GD-70D can be used as a stand-alone device, offering a number of communication protocols to existing PLC systems, or can be integrated with RKI’s Beacon series of single and multi-channel controllers.
All GD-70D transmitters include a large, easy to read integral LCD display, tri-color bar graph for visual notification of alarm status, programmable low and high alarm relays, and fault relay. Pump flow is self-tuning for maintenance-free operation. Because all GD-70D base units are identical, sensors can be interchanged with no programming or tools required, resulting in maximum flexibility to the user.
- Monitor combustibles, O2, and a wide range of toxics
- Plug and play smart sensors retain calibration and sensor data
- Common platform (Main unit / Sensor / Pump) for all detection methods
- Universal main unit (all sensor types)
- Multifunctional sensor unit (New Intelligent sensor)
- No internal tubing (main unit) / No coil (pump)
- Front access, no tool required, easy sensor and pump replacement
- Large size LCD screen
- Various communication methods available (4-20mA, NT and PoE)
- Minimal maintenance cost through enhanced troubleshooting firmware functions
- Small mounting space
- Environmentally friendly
- Wide variety of sensors available
ESU Gas Detected ACGIH TLV-TWA
Detection Range
Ammonia NH3 25 ppm
75 ppm
Arsine AsH3 5 ppb
0.2 ppm
Bromine BR2 0.1 ppm
1 ppm
Carbon Monoxide CO 25 ppm
75 ppm *
150 ppm
300 ppm *
Chlorine Cl2 0.5 ppm
3 ppm
1.5 ppm *
Chlorine Trifluoride ClF3 (C) 0.1 ppm
0.6 ppm
Diborane B2H6 0.1 ppm
0.3 ppm
Disilane Si2H6 (C) 2 ppm
15 ppm
Dimethylamine (CH3)2NH 5 ppm
15 ppm
Diethylamine (CH3CH2)2NH 5 ppm
15 ppm
Fluorine F2 1 ppm
3 ppm
Germane GeH4 (C) 2 ppm
0.8 ppm
Hydrogen Bromide HBr (C) 2 ppm
6 ppm,
9 ppm *Hydrogen Chloride HCI (C) 2 ppm
6 ppm,
15 ppm *Hydrogen Fluoride HF 0.5 ppm
9 ppm,
3 ppm *Hydrogen Selenide H2Se 0.05 ppm
0.2 ppm
Methylamine CH3NH2 5 ppm
15 ppm
Nitric Oxide NO 25 ppm
100 ppm
Nitrogen Dioxide NO2 3 ppm
15 ppm
Nitrogen Trifluoride NF3 10 ppm
30 ppm
Ozone O3 0.1 ppm
0.6 ppm
Phosphine PH3 0.3 ppm
1. ppm
Silane SiH4 5 ppm
15 ppm
Sulfur Dioxide SO2 —
6 ppm
Trimethylamine (CH3)3N 5 ppm
15 ppm
SGU Gas Detected ACGIH TLV-TWA
Detection Range
Methane CH4 1,000 ppm
2,000 ppm
5,000 ppm *
Dichloroethene C2H2CL2 200 ppm
600 ppm
Isopropyl Alcohol CH3CHOHCH3 200 ppm
2,000 ppm
Propane CH3H8 1,000 ppm
2,000 ppm
5,000 ppm *
Methyl Alcohol CH3OH 200 ppm
1,000 ppm
2,000 ppm *
Hydrogen H2 —
500 ppm *
1,000 ppm *
2,000 ppm
Difluoromethane R-32 1,000 ppm
2,000 ppm
Fluoro Methane R-41 1,000 ppm
2,000 ppm
Carbonyl Sulfide COS —
2,000 ppm
Dichloromethane CH2CL2 50 ppm
2,000 ppm
NCU Gas Detected LEL % Vol. Levels
Detection Range
Methane CH4 5% Vol.
100% LEL
2.0 Vol.
Isobutane i-C4H10 1.8% Vol.
100% LEL
Hydrogen H2 4% Vol.
2.0 Vol.
SSU Gas Detected ACGIH TLV-TWA
Detection Range
Trimethyl Silane TMS —
15 ppm
Trimethoxysilane TRIMOS —
15 ppm
Tetraethyl Orthosilicate TEOS 10 ppm
15 ppm
OSU Gas Detected ACGIH TLV-TWA
Detection Range
Oxygen O2 —
25% Vol.
* Specifications subject to change without notice.
MAIN UNIT
Model | GD-70D | GD-70D-NT | GD-70D-ET |
Communication | 4-20mA DC | DC power line communication | PoE Method |
Detection principle | Different type depending upon sensor unit and detectable gas (see table) | ||
Sampling method | Sample drawing types (auto-adjustment of flow rate) 0.5 / min +/-10% | ||
Display |
| ||
Gas alarms | Two alarm levels: 1st alarm – Red 2nd alarm – Red Fault alarm: Yellow | ||
External output | 1st, 2nd, and trouble alarms : Relay contact output for each alarm | ||
Self diagnostic function | System failure, sensor failure, flow failure, communication error NT / ET / Analog | ||
Datalogging | Event history, alarm history, calibration history. Alarm trend (180 sec before / after 1st alarm) | ||
Operation temp. & humidity | 0 ~ 40ºC, 30 ~ 70% RH (non-condensing) | ||
Operating settings | All operational settings are user adjustable through front panel | ||
Power requirements | DC 24V+/- 10%, approx 1.5W (Max 4W including sensor unit) Note: Approx. 2.5W (Max 5W) with SGU sensor unit | PoE standard arrangement | |
Dimensions | 2.8”W x 4.7”H x 5.9”D (70W x 120H x 150Dmm) | ||
Weight | Approx. 0.9kg (2.0lbs), including sensor unit | ||
Mounting | Wall-mounting base plate by 2 or 3 screws | ||
Sampling tubing | 4 x 6mm PTFE tubing recommended. Tube fittings provided as standard accessories | ||
Bushing | Cable type varies depending on communication method (Cable bushing optional) |
SENSOR UNIT
Model | ESU | SGU | SSU | OSU | NCU |
Detection Principle | Electro-chemical cell | Semi-conductor | Pyrolysis-particle | Galvanic cell | Catalytic combustion |
Gas detected and detection range | Refer to list of detectable gases | 0-2000ppm H2, CH4, or CH2F2 (R-32) in air and others | 0-15ppm TEOS in air | 0-25% O2 in air | 0-100% LEL H2, CH4, and others |
Self diagnosis function | Sensor trouble, system failure | ||||
Date logging function | Event history, alarm history, calibration history, Alarm trend (60 sec. before/after 1st alarm) |
PYROLYSER UNIT
Model | PLU-70 |
Application | NF3 / TEOS gases detected in air |
Usage | Used by connecting to “GD-70D” (Main unit) |
Power Lamp | LED (Green color) Normal: Light-on Warming-up: Flashing at every 1 sec interval |
Self-diagnostic function | Pyrolyser unit trouble Fan Trouble System trouble |
Operating temp. & humidity | 0-40° C, 30-70% RH (non-condensing) |
Operational settings | All operational settings are user adjustable through front panel. |
Power requirements | DC 24V+/- 10%, approx. 25W (max) |
Dimensions | 2.8”W x 4.7”H x 5.9”D (70W x 120H x 150Dmm) |
Weight | Approx. 1.2kg (2.6lbs) |
Mounting | Wall-mounting base plate by 2 or 3 screws |
Sampling | 4x6mm PTFE tubing recommended. Tube fittings provided as standard accessories |
Bushing | 1.25sq 2 core cable for power supply DC24V (Cable bushing optional) |