CO-04

Portable Gas Detector CO-04

  • Smart interchangeable sensors
  • Wide range of toxic gases
  • Unique extender cable for remote monitoring
  • Approx. 54mm(W) x 67mm(H) x 24mm(D)(excluding projections)
  • Approx. 93g
  • 250 hours of continuous operation
  • AAA alkaline or Ni-MH(eneloop) batteries(x2)
  • Audible / visual / vibration alarms
  • Datalogging standard
  • Impact resistant protective rubber boot
  • Description
  • Applications
  • Features
  • Specifications
  • Download

Built around RKIs latest smart sensor technology, the CO-04 is a versatile single toxic gas monitor. The smart sensors are interchangeable, with the CO-04 automatically recognizing any sensor change without any set up or configuration changes. The sensors calibration information also stays with each sensor. Weighing only 7.6 ounces, it has many features which set it apart from the competition. For example, it offers sensors for Ammonia (NH3), Arsine (ASH3), Carbon Monoxide (CO), Chlorine (Cl2), Hydrogen Cyanide (HCN), Hydrogen Sulfide (H2S), Phosphine (PH3), and Sulfur Dioxide (SO2). The SC-01s unique extender cable allows the sensor to be attached to the end of a 10 foot cable for remote monitoring and quick response

  • Utilities
  • Personal monitoring
  • Refineries / petrochemical
  • Chemical plants
  • Hazmat response
  • Water / wastewater treatment
  • Semiconductor plants

Smart interchangeable sensors
Remote monitor capability by optional extender cable (3m)
Approx. 54mm(W) x 67mm(H) x 24mm(D)(excluding projections)
250 hours of continuous operation
AAA alkaline or Ni-MH(eneloop) batteries(x2)

CategoryPortable gas detector
TypeSingle Gas
Gas typeToxic
Detection gasCO[CO-04]
CO(Reduced H2 interference)[CO-04(C-)]
Principle of detectionElectrochemical type
Detection range0-300ppm / 300-2000ppm
Alarm setpoints1st 25ppm / 2nd 50ppm / 3rd 1200ppm / TWA 25ppm / STEL 200ppm
Sampling methodDiffusion
Display of alarmFlashing light / buzzer / vibration
Explosion protected constructionIntrinsically safe
IP ratingIP66/67 (currently under testing)
ApprovalsIECEx/ATEX/CE (pending)
Power sourceAAA alkaline or Ni-MH(eneloop) batteries(x2)
Battery lifeApprox. 9000hours(AAA alkaline)/Approx. 6000hours(Ni-MH)[CO-04]
Approx. 6200hours(AAA alkaline)/Approx. 4200hours(Ni-MH)[CO-04(C-)]
DimensionsApprox. 54mm(W) x 67mm(H) x 24mm(D)(excluding projections)
WeightApprox. 93g
Operating temperature range-20℃ to +50℃ (no sudden changes)(Approx. 15-minute temporry use environment: -40℃ to +60℃[no sudden changes])
Operating humidity range10 to 90%RH (no condensation)(Approx. 15-minute temporry use environment: 0 to 95%RH[no condensation])

Download datasheet